繁體版
0 item(s)

Seismic monitoring system with display (SW-74SI) Item No:Seismic monitoring system with display (SW-74SI)

Seismic monitoring system with display (SW-74SI)Item No:Seismic monitoring system with display (SW-74SI)

High-end model of SW-74 which can indicates SI (Spectrum Intensity) value.

Multi-functional equipment which can be set acceleration, seismic intensity and SI value individually.

ItemSpecification
Display element STN monochrome LCD with touch switch / back light color : green / orange / red
Display
contents
Earthquake monitor display Present time
Earthquake generation display Earthquake generation time, maximum acceleration, seismic intensity scale, alarm operation
Alarm hold display Avobe + reset button (whole reset of alarm / buzzer)
Setting display Trigger, alarm, date & time
Maintenance display Pickup test, earthquake history
Alarm and buzzer Upper limit 3-step (ALM1–3), individual setting, buzzer for point,
Alarm setting value : 0.1 to 999.9 (gal / seismic intensity scale / Kine)
Setting interval : 0.1 step,0.0 is alarm operation OFF (seismic intensity scale alarm is set byinstrumental seisimic intensity value)
Extra alarm Alarm step Upper limit 7-step (ALM4–10), individual setting (acceleration / seismic intensity scale / SI value/any setting is possible)
Alarm setting value 0.1 – 999.9 (gal/seismic intensity scale / Kine) setting interval 0.1 step,
0.0 is alarm operation OFF (seismic intensity scale alarm is set by instrumental seismic intensity value)
Alarm contact 1a contact (photo MOS relay) independent COM 2-point (ALM1–5, ALM 6–10, each 1-point)
Contact rating 200 V – 0.65 A (AC / DC, peak value)
Alarm and buzzer
reset method
a. Automatic reset by an internal timer 1 – 9999 sec. (setting interval 1 sec., 0 is automatic reset OFF)
b. External reset terminals (all steps reset by non-voltage [a] contact)
c. Reset button on the touch panel (effective on alarm display)
FAULT alarm (Power failure or system abnormal) 1a / 1b contact switching type
Contact rating : 2 A 30 VDC (maximum allowable voltage / current : 220 VDC / 2A)
Serial output For maintenance (conforms to RS232C ) : MC1 (switch over)
For external display (conforms to RS422) : MC2
For printer (conforms to RS232C): MC2
Back up unit Backup time > 10 min. (ready time), charging time < 48 hours
(no function at the operation by optional power 24 VDC )
Mounting method Wall hanging
Operational temperature
range
0 to + 50 °C
Operational humidity range 10 to 85 %RH (non-condensing)
Power supply AC100 V ±10 %, less than 50 VA DC24 V ±10 %, less than 70 W (option)
Mass Aprox. 3 kg